equipment hosting in a tower (large set);
equipment placement in the middle section of the tower;
space in the tower area near the container;
equipment hosting in a switch cabinet.
Technical parameters for equipment in the tower (set):
No. | Parameter | Meaning |
1. | Definition of service | Space for communication equipment in the tower (kit) with the possibility of connecting the equipment to the fibre optic and electrical cables installed in the tower |
2. | Service | Tower equipment (kit) |
3. | Total size and location of equipment to be hosted | Maximum 2,5 m2 of wind area* and 200 kg of weight for antenna equipment in the upper part of the tower (above 50 m), radio equipment (RRU) and other equipment at a height of about 50 m. |
4. | Total capacity of the hosted equipment | The total combined electrical power of all installed equipment, including equipment mounted on the tower and in switch cabinets, is up to 3 kW. |
5. | Use of fibre optic cables in the tower | Access to fibre optic cables installed in the tower: up to 24 fibres in a singlemode fibre optic cable connected in an optical distribution box or a hybrid electrical and optical distribution box at the top of the tower, at a height of about 50 m, and at the bottom of the tower, in cabinets or areas dedicated to operators' equipment; or the possibility of installing one's own cables in the tower, up to a maximum of 0.11 kg/m, up to a maximum of 11 mm in diameter. |
6. | Use of electrical cabling in the tower | Access to power cables installed in the tower: one pair of 2x25 mm2 or one pair of 2x16 mm2 48V DC power cables in a power distribution box or a hybrid power and fibre optic distribution box at the top of the tower, at a height of about 50 m, and at the bottom of the tower, in cupboards or areas dedicated to the operator's equipment, or the possibility of installing one or more of your own power cables in the tower, up to a maximum of 1,2 kg/m, up to a maximum of 26 mm in diameter. |
7. | Requirements for hosting, securing equipment in tower | The installation of communication equipment in the tower shall be carried out in accordance with a radiotechnical design drawn up and approved in accordance with the requirements laid down by law. The equipment to be installed in the tower shall be mounted on brackets which are attached to the ring structures or to the tower structures |
8. | Purpose | The intended use and technical characteristics of the services must comply with the requirements laid down in these State aid schemes: 183/2009 – Lietuva, SA.34166, SA.36132, SA.46372, SA.49614 ir SA.63098. |
*wind area calculated as the sum of the wind areas of all the equipment, which are calculated by multiplying the two largest dimensions of each piece of equipment (e.g. height and width of the equipment) or by preparing a separate design, where the wind area is calculated taking into account the exact area of the equipment, the mounting directions, etc.
Technical parameters for the equipment in the tower (large set):
No. | Parameter | Meaning |
1. | Definition of service | Space for communication equipment in the tower (kit) with the possibility of connecting the equipment to the fibre optic and electrical cables installed in the tower |
2. | Service | Equipment in the tower (large set) |
3. | Total size and location of equipment to be hosted | Maximum 5,5 m2 of wind area* and 500 kg of weight for antenna equipment in the upper part of the tower (above 50 m), radio equipment (RRU) and other equipment at a height of about 50 m. |
4. | Total capacity of the hosted equipment | The total combined electrical power of all installed equipment, including equipment mounted on the tower and in switch cabinets, is up to 6 kW. |
5. | Use of fibre optic cables in the tower | Access to fibre optic cables installed in the tower: up to 24 fibres in a singlemode fibre optic cable connected in an optical distribution box or a hybrid electrical and optical distribution box at the top of the tower, at a height of about 50 m, and at the bottom of the tower, in cabinets or areas dedicated to operators' equipment; or the possibility of installing one's own cables in the tower, up to a maximum of 0.11 kg/m, up to a maximum of 11 mm in diameter. |
6. | Use of electrical cabling in the tower | Access to power cables installed in the tower: one pair of 2x25 mm2 or one pair of 2x16 mm2 48V DC power cables in a power distribution box or a hybrid power and fibre optic distribution box at the top of the tower, at a height of about 50 m, and at the bottom of the tower, in cupboards or areas dedicated to the operator's equipment, or the possibility of installing one or more of your own power cables in the tower, up to a maximum of 1,2 kg/m, up to a maximum of 26 mm in diameter. |
7. | Requirements for hosting, securing equipment in tower | The installation of communication equipment in the tower shall be carried out in accordance with a radiotechnical design drawn up and approved in accordance with the requirements laid down by law. The equipment to be installed in the tower shall be mounted on brackets which are attached to the ring structures or to the tower structures |
8. | Purpose | The intended use and technical characteristics of the services must comply with the requirements laid down in these State aid schemes: 183/2009 – Lietuva, SA.34166, SA.36132, SA.46372, SA.49614 and SA.63098. |
*wind area calculated as the sum of the wind areas of all the equipment, which are calculated by multiplying the two largest dimensions of each piece of equipment (e.g. height and width of the equipment) or by preparing a separate design, where the wind area is calculated taking into account the exact area of the equipment, the mounting directions, etc.
Technical parameters for equipment space in the middle section of the tower:
No. | Parameter | Meaning |
1. | Definition of service | Antenna site in the middle section of the tower (between 30 and 50 m). |
2. | Service | Space for equipment in the middle section of the tower |
3. | Total size and location of equipment to be hosted | Space for one antenna (maximum 0.3 m2 of wind area* and 30 kg of weight) in the middle part of the tower (30 to 50 m height). |
4. | Total capacity of the hosted equipment | The total combined electrical power of all installed equipment, including equipment mounted on the tower and in switch cabinets, is up to 0.5 kW. |
5. | Use of fibre optic cables in the tower | Access to fibre optic cables installed in the tower: up to 24 fibres in a singlemode fibre optic cable connected in an optical distribution box or a hybrid electrical and optical distribution box at the top of the tower, at a height of about 50 m, and at the bottom of the tower, in cabinets or areas dedicated to operators' equipment; or the possibility of installing one's own cables in the tower, up to a maximum of 0.11 kg/m, up to a maximum of 11 mm in diameter. |
6. | Use of electrical cabling in the tower | The possibility of installing your own power cables in the tower, weighing up to 1.2 kg/m and with a diameter of up to 26 mm. weighing up to 1.2 kg/m and with a diameter of up to 26 mm. |
7. | Requirements for hosting, securing equipment in tower | The installation of communication equipment in the tower shall be carried out in accordance with a radiotechnical design drawn up and approved in accordance with the requirements laid down by law. The equipment to be installed in the tower shall be mounted on brackets which are fixed to the ring structures or to the tower structure. |
8. | Purpose | The intended use and technical characteristics of the services must comply with the requirements laid down in these State aid schemes: 183/2009 – Lietuva, SA.34166, SA.36132, SA.46372, SA.49614 and SA.63098. |
*wind area is calculated as the sum of the wind areas of all the equipment, which is calculated by multiplying the two largest dimensions of each piece of equipment, e.g. the height and width of the equipment.
Location in the tower area near the container Technical parameters:
No. | Parameter | Meaning |
1. | Definition of service | Space for a cabinet for operators' equipment in the tower area, with the possibility of connecting the equipment to the installed fibre-optic and electrical cables. |
2. | Service | Location on the tower site |
3. | Local specification | A solid base has been provided for the construction of an outdoor cabinet for telecommunications equipment. |
4. | Requirements for hosting, securing equipment in tower | Cabinets shall be installed on a purpose-built solid base. The cabinets shall be of metallic construction, suitable for outdoor use, and shall have a protection class not less than IP54, with protection against vandalism. |
5. | Purpose | The intended use and technical characteristics of the services must comply with the requirements laid down in these State aid schemes: 183/2009 – Lietuva, SA.34166, SA.36132, SA.46372, SA.49614 and SA.63098. |
Last updated: 17-07-2024